AGDS-MCM v2 Sixteen channel Gas Detection System
The AGDS-MCM is a gas monitoring system designed for use in areas of potential gas escape and build-up.

The AGDS-MCM v2 is a gas detection system for the monitoring of common gases.
Providing gas monitoring of up to sixteen Medem detectors for the detection of natural gas, LPG, carbon monoxide, carbon dioxide and oxygen depletion.
In the event of a high alarm from one of the detectors, the system can activate a relay, beacon or sounder. Low alarm indication is also given. The OLED will display appropriate information about alarm situations and detector status.
“Out of hours” monitoring and ventilation control
Even with the system switched off the AGS-MCM v2 can still be used to monitor for carbon monoxide and carbon dioxide via its 0-10v output and BMS relays. Should there be an issue from a solid fuel appliance it can raise an alarm or switch ventilation on via a relay. This provides additional safety monitoring particularly if solid fuel appliances are installed.
Remote Indications
All system states and alerts can be remotely monitored and indicated via our “”BMS” relays. There are five protentional free relays each of which can configured separately.
Product Features
- Gas detection (1-16 detectors)
- Multiple different gas types
- Five settable BMS relays
- Event log
- Engineer functions
Gas Detectors
The panel can monitor up to 6 detectors directly, and 16 with an additional AD-PP power pack.
The current range is:


Click here to find out more about our product warranty
Download Our Detector Location Guide
AGDS-MCM v2 Sixteen channel Gas Detection System
Specifications
| Power | 230 VAC – 3 amp fused spur. |
| Product Dimensions | 255mm x 180mm x 80mm |
| Weight | |
| Temperature Range | -5° to 55°C. |
| Humidity | 20% to 90%RH Non-Condensing. |
| Ingress Protection | IP64 |
| Housing Material | ABS Plastic |
| Colour | Grey |
| Mounting | Wall Mount |
| Sensors | Pellistor, Toxic, Oxygen, NDIR. |
| Outputs & Connections | 2x Potential free change over relays. (Mains rated) |
| 3x Potential free change over relays. (SLEV) | |
| 1x 12volt supply rails. |
Alarm Types
Fixed low and high alarm peak levels, high alarm activation will latch and isolate the connected gas valve.
Low & High Alarms
Methane/Natural Gas (CH4) & Propane (C3H8)
- 5% Low alarm
- 10% High alarm
Carbon Monoxide (CO)
- 20PPM Low Alarm
- 30PPM High Alarm
Carbon Dioxide (CO2) – Selectable
- 1500PPM
- 2200PPM
- 2800PPM
- 4000PPM
- 5000PPM
Oxygen (O2) Depletion
- 19.5% Pre Alarm
- 18% Full Alarm
AGDS-MCM v2 Sixteen channel Gas Detection System Manuals
Product and Installation Guides
AGDS-MCM v2 Sixteen channel Gas Detection System Warranty and Service

All our products come with a 5-year warranty
Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of its products.
This applies to the main panels and sender units, gas detectors carry a 2-year warranty.

Why not let us commission your system and receive a 10-year Warranty?
Where we’ve commissioned an installed system, the warranty is extended from five to ten years. At the time of commissioning, photos and gas pressure readings are recorded along with other relevant details of the installation. A 24-hour helpline number and the serial number is attached with the panel and all details are then entered on to the Medem database.
Service
The panel and sensors must be re-commissioned and tested every 12 months as a minimum but with consideration of every 6 months dependent on gas type and environment. Medem offers cost-effective yearly service plan options.
AGDS-MCM v2 Sixteen channel Gas Detection System Image Gallery



Related Products


Inair CO2 Monitoring
- Designed for Gas Detection
- Standalone CO2 detection
- Can display daily min, max and ave values
Product not found.

Pro-elite 32 Channel Gas Detection System
- 32 Channel gas detection system
- Fully programable system
- Battery backup
- Wide range of gas detectors including ATEX