Boiler Rooms

AGDS-2em v2 Single or Two Channel Gas Detection System with Valve Control

The AGDS-2em V2 is a gas detection system with valve isolation. Designed for in boiler houses, plant rooms and areas with a risk of gas escape or build up..

AGDS-2 EM v2

The AGDS-2em V2 is a gas detection system with gas valve isolation.

In the event of a high alarm from one of the detectors, the system will isolate the gas valve and operate any configured relays, beacons or sounders. Low alarm indication is also given.

Single or Two Channel

Up to two Medem gas detectors can be connected for the detection of natural gas, LPG or carbon monoxide.

Panel controls include an ‘Emergency Stop’, ‘Mute’ and ‘Reset’ buttons.

Features

The LED’s will display appropriate information about alarm situations and detector status.

Panel controls include ‘Mute’, ‘Reset’ and Emergency Stop buttons. Remote emergency stop buttons and thermal links can be monitored and there is also a fire alarm input which will close the gas valve when activated.

Remote Indications

There are two change over mains rated relays which can be used to activate a beacon/sounder, a fan or signal to a BMS system.

Each relay is able to be set to report one of the below statuses:

  • Generic Alarm
  • Low Alarm
  • High Alarm
  • Detector Fault.
  • Gas detection (1-2 detectors)
  • Multiple different gas types
  • Panel mounted Emergency Stop Button
  • EM Stop, Fire Alarm and thermal link monitoring
  • Settable mains rated relay (Low/High Alarm, Detector Alert, EM stop & Gas On conditions)
  • Engineer functions

The panel can monitor up to 4 detectors directly.

The current range is:

Click here to find out more about our product warranty

Download Our Detector Location Guide

Power230 VAC – 3 amp fused spur.
Product Dimensions180mm x 130mm x 60mm
Weight
Temperature Range-5° to 55°C.
Humidity20% to 90%RH Non-Condensing.
Ingress ProtectionIP64
Housing MaterialABS Plastic
ColourGrey
MountingWall Mount
SensorsPellistor, Toxic, Oxygen, NDIR.
Outputs & Connections230v Gas Valve
2x Potential free change over relays. (Mains rated)

Alarm Types

Fixed low and high alarm peak levels, high alarm activation will latch and isolate the connected gas valve.

Low & High Alarms

Methane/Natural Gas (CH4) & Propane (C3H8)

  • 5% Low alarm
  • 10% High alarm

Carbon Monoxide (CO)

  • 20PPM Low Alarm
  • 30PPM High Alarm

Carbon Dioxide (CO2)

  • 2800PPM
  • 5000PPM

Oxygen (O2)

  • 19.5%
  • 18.0%

All our products come with a 5-year warranty

Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of its products.

This applies to the main panels and sender units, gas detectors carry a 2-year warranty.

Why not let us commission your system and receive a 10-year Warranty?

Where we’ve commissioned an installed system, the warranty is extended from five to ten years. At the time of commissioning, photos and gas pressure readings are recorded along with other relevant details of the installation. A 24-hour helpline number and the serial number is attached with the panel and all details are then entered on to the Medem database.

Service

The panel and sensors must be re-commissioned and tested every 12 months as a minimum but with consideration of every 6 months dependant on gas type and environment. Medem offers cost-effective yearly service plan options which include detector exchange to assist in service budgeting.

Related Products

AGDS-MC v2 Boiler House Multi-channel Gas Detection System

AGDS-MC v2 Sixteen channel Gas Detection System with Valve Isolation

  • Designed for Boiler Rooms
  • 16 Channel Gas detection system
  • Valve isolation
  • Event log

View Product
AGDS-4 4 channel Gas Detection System with Valve Control

AGDS-4 4 channel Gas Detection System with Valve Control

  • Designed for Boiler Rooms
  • 4 Channel Gas detection system
  • Valve isolation

View Product
AGDS-V Four Channel Gas Detection System

AGDS-V Four Channel Gas Detection System with Valve Isolation

  • Designed for Boiler Rooms
  • 4 Channel Gas detection system
  • Programmable relays

View Product
SEC B v5

SEC-B v5 Gas Proving and Detection system

  • Designed for Boiler Rooms
  • Combined gas detection and pressure proving system
  • Automatically resets after a power failure or fire alarm
  • Reduces the potential for site down time and frozen pipes

View Product