SafeAir CM Ventilation Interlocking with Built-in Current Monitoring
The SafeAir CM offers a simple single panel package for ventilation interlocking a commercial kitchen to aid sites in meeting BS6173:2020 and IGEM/UP19.

The SafeAir CM is a ventilation and gas interlock system for commercial kitchens.
Ventilation Interlock
Interlocking can be achieved with either airflow switches or the built-in two channel current monitor. The built in current monitor can be “learnt” with minimum and maximum fan current loads, each current monitor has a sensitivity range of 30 milliamps to 20 amps (max).
It is a requirement (see BS 6173 & UP19) that any mechanical ventilation within a kitchen environment (supply and extract) is switched on and running before the use of any gas appliances can take place. If the ventilation is not switched on, the LCD display informs the operator of the fans that are off. It then advises to switch them on and reset the panel.
Gas Detection
Up to four CO2 gas detectors can be connected to the system, low level alerts will cause a audible tone and visual message on screen, high level alerts will additionally isolate the gas supply.
Medem detectors can be used to monitor the carbon dioxide level to ensure that HSE set levels are not exceeded.
Gas Valve Isolation
In the event of fan failure, a high CO2 alert or the activation of the emergency circuit the connected gas isolation valve will be closed.
Product Features
- Ventilation Interlock
- In-built two-channel current monitoring
- Simple button press learn feature for current monitoring set-up
- Gas Detection (1-4 detectors)
- Carbon Dioxide Level Monitoring
- Settable SELV relay (Low/High Alarm, Detector Alert, EM stop & Gas On conditions)
- EM stop & Fire Alarm monitoring
- Panel mounted Emergency Stop Button with a facility to monitor remote buttons.
Gas Detectors
The panel can monitor up to 4 detectors
The current range is:


SafeAir CM Ventilation Interlocking with Built-in Current Monitoring
Specifications
| Power | 230 VAC – 3 amp fused spur. |
| Product Dimensions | 255mm x 180mm x 80mm |
| Weight | |
| Temperature Range | -5° to 55°C. |
| Humidity | 20% to 90%RH Non-Condensing. |
| Ingress Protection | IP64 |
| Housing Material | ABS Plastic |
| Colour | Grey |
| Mounting | Wall Mount |
| Sensors | Pellistor, Toxic, Oxygen, NDIR. |
| Outputs & Connections | 230v supply to gas valve |
| 1x Protentional free change over relays. (Mains rated) | |
| 2x Airflow switch connections | |
| 2x Current Monitor (Fan interlocking) | |
| Emergency stop |
Alarm Types
Fixed low and high alarm peak levels, high alarm activation will latch and isolate the connected gas valve.
Peak Alarms
Methane/Natural Gas (CH4) & Propane (C3H8)
- 5% Low alarm
- 10% High alarm
Carbon Monoxide (CO)
- 20PPM Low Alarm
- 30PPM High Alarm
Carbon Dioxide (CO2) – Selectable
- 2800PPM
- 5000PPM
SafeAir CM Ventilation Interlocking with Built-in Current Monitoring Manuals and Standards
Product and Installation Guides
SafeAir CM Ventilation Interlocking with Built-in Current Monitoring Warranty and Service

All our products come with a 5-year warranty
Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of its products.
This applies to the main panels and sender units, gas detectors carry a 2-year warranty.

Why not let us commission your system and receive a 10-year Warranty?
Where we’ve commissioned an installed system, the warranty is extended from five to ten years. At the time of commissioning, photos and gas pressure readings are recorded along with other relevant details of the installation. A 24-hour helpline number and the serial number is attached with the panel and all details are then entered on to the Medem database.
Service
Required every 12 months (or 6 months depending on gas type and environment); cost-effective yearly service plans available
SafeAir CM Ventilation Interlocking with Built-in Current Monitoring Image Gallery




Related Products

GPPS-evo v4 Laboratory Gas Pressure Proving System
- Designed for Laboratories
- Gas pressure proving
- Optional CO2 detection

SEC-K v5 Ventilation Interlock and Gas Proving System
- Designed for Commercial Kitchens
- Ventilation Interlock
- Gas Pressure Proving
- Electric Isolation
- CO₂ monitoring for environmental monitoring and fan control

SafeAir Commercial Kitchen Ventilation Interlocking System
- Designed for Commercial Kitchens
- Ventilation Interlock
- Checks for gas leaks at switch-on
- CO₂ monitoring for environmental monitoring and fan control