SafeAir (GP) Gas Proving and Ventilation Interlocking for Commercial Kitchens
The SafeAir (GP) offers a simple cost-effective panel for ventilation interlocking and gas pressure proving in a commercial kitchen.

The SafeAir (GP) is a ventilation interlock and gas proving system for commercial kitchens.
Ventilation Interlock
Interlocking can be achieved with the use of airflow switches or current monitoring.
It is a requirement (see BS 6173 & UP19) that any mechanical ventilation within a kitchen environment (supply and extract) is switched on and running before the use of any gas appliances can take place. If the ventilation is not switched on, the LCD display informs the operator of the fans that are off. It then advises to switch them on and reset the panel.
Gas Pressure Proving
Gas proving must be fitted in any commercial kitchen which has appliances fitted without flame failure devices (FFD’s). As explained further in the article
“why fit gas pressure proving in a commercial kitchen?” gas proving should be considered for the long-term benefit and safety of the site when considering other gas standards and that the majority of leaks identified are before the FFD’s.
Using our patented differential pressure proving method the system checks the gas pipework and appliances in a kitchen for gas leaks. It also monitors for low pressure and overpressure without opening the solenoid valve, making it the only truly safe method of proving available.
see Why choose Medem differential pressure proving?
Gas Detection
Up to four CO2 gas detectors can be connected to the system, low level alerts will cause a audible tone and visual message on screen, high level alerts will additionally isolate the gas supply.
Medem detectors can be used to monitor the carbon dioxide level to ensure that HSE set levels are not exceeded.
Gas Valve Isolation
In the event of fan failure, a high CO2 alert or the activation of the emergency circuit the connected gas isolation valve will be closed.
Product Features
- Gas Pressure Proving
- Ventilation Interlock
- In-built two-channel current monitoring
- Simple button press learn feature for current monitoring set-up
- Gas Detection (1-4 detectors)
- Carbon Dioxide Level Monitoring
- Settable SELV relay (Low/High Alarm, Detector Alert, EM stop & Gas On conditions)
- EM stop & Fire Alarm monitoring
- Panel mounted Emergency Stop Button with a facility to monitor remote buttons.
Gas Detectors
The panel can monitor up to 4 detectors
The current range is:


Click here to find out more about our product warranty
SafeAir (GP) Commercial Kitchen Ventilation Interlock and gas Proving System
Specifications
| Power | 230 VAC – 3 amp fused spur. |
| Product Dimensions | 180mm x 130mm x 60mm |
| Weight | |
| Temperature Range | -5° to 55°C. |
| Humidity | 20% to 90%RH Non-Condensing. |
| Ingress Protection | IP64 |
| Housing Material | ABS Plastic |
| Colour | Grey |
| Mounting | Wall Mount |
| Sensors | Pellistor, Toxic, Oxygen, NDIR. |
| Outputs & Connections | 2x Airflow switch connections |
| 1x Potential free change over relays. (SLEV) | |
| 1x 12volt supply rail. |
Alarm Types
Fixed low and high alarm peak levels, high alarm activation will latch and isolate the connected gas valve.
Peak Alarms
Methane/Natural Gas (CH4) & Propane (C3H8)
- 5% Low alarm
- 10% High alarm
Carbon Monoxide (CO)
- 20PPM Low Alarm
- 30PPM High Alarm
Carbon Dioxide (CO2) – Selectable
- 2800PPM
- 5000PPM
SafeAir (GP) Commercial Kitchen Ventilation Interlock and gas Proving System Manuals and Standards
Product and Installation Guides
SafeAir (GP) Commercial Kitchen Ventilation Interlock and gas Proving System Warranty and Service

All our products come with a 5-year warranty
Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of its products.
This applies to the main panels and sender units, gas detectors carry a 2-year warranty.

Why not let us commission your system and receive a 10-year Warranty?
Where we’ve commissioned an installed system, the warranty is extended from five to ten years. At the time of commissioning, photos and gas pressure readings are recorded along with other relevant details of the installation. A 24-hour helpline number and the serial number is attached with the panel and all details are then entered on to the Medem database.
Service
Required every 12 months (or 6 months depending on gas type and environment); cost-effective yearly service plans available
SafeAir (GP) Commercial Kitchen Ventilation Interlock and gas Proving System Image Gallery

Related Products

SafeAir Commercial Kitchen Ventilation Interlocking System
- Designed for Commercial Kitchens
- Ventilation Interlock
- Checks for gas leaks at switch-on
- CO₂ monitoring for environmental monitoring and fan control

SEC-K v5 Ventilation Interlock and Gas Proving System
- Designed for Commercial Kitchens
- Ventilation Interlock
- Gas Pressure Proving
- Electric Isolation
- CO₂ monitoring for environmental monitoring and fan control

SafeAir CM (GP) Ventilation Interlock and Gas Proving System with Built-in Current Monitoring
- Designed for Commercial Kitchens
- Gas Pressure Proving
- Ventilation Interlock
- Checks for gas leaks at switch-on
- CO₂ detectors for environmental monitoring and fan control

SafeAir (GP) Commercial Kitchen Ventilation Interlock and gas Proving System
- Designed for Commercial Kitchens
- Gas Pressure Proving
- Ventilation Interlock
- Checks for gas leaks at switch-on
- CO₂ detectors for environmental monitoring and fan control