The AGDS-M is a four channel gas detection system designed for environmental monitoring within boiler rooms, cellars, gas stores and areas with a risk of gas escape or build-up.

A low alarm indication is given on the control panel including ‘Mute’, ‘Reset’. There are two change over mains rated relays which can be used to activate a beacon/sounder, a fan or signal to a BMS system.

Each relay is able to be set to report one of the below statuses:

  • Low Alarm
  • High Alarm
  • Detector Fault
  • Generic Alarm


If you require further information about this product please call us on 0161 233 0600 or email at enquiries@medem.co.uk and we’ll be more than happy to help.

 

Description

> Low Alarm <
> > Compact <
> 1 to 4 detectors <
> Five different gas detector types <
> Simple to install <
> Two settable mains rated relays <
> Clear OLED display <

Two settable mains rated relays for BMS, beacon or fan activation.
Low Alarm • High Alarm • Detector Fault • Generic Alarm.

 


Product and Installation Guides
⤓ AGDS-M | Product and Installation Guide

 


All our products come with a 5-year warranty
Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of its products.
This applies to the main panels and sender units, gas detectors carry a 2-year warranty.

Why not let us install your system and receive a 10-year Warranty?
Where we’ve commissioned an installed system, the warranty is extended from five to ten years. At the time of commissioning, photos and gas pressure readings are recorded along with other relevant details of the installation. A 24-hour helpline number and the serial number is attached with the panel and all details are then entered on to the Medem database.

 

Additional information

Product Dimensions

180mm x 130mm x 70mm

Gas Detection

The panel can except a maximum of four detectors. The current range is:
Methane/Natural Gas (CH4), Propane (C3H8), Carbon Monoxide (CO) Carbon Dioxide (CO2) and Oxygen (O2) Depletion

Alarm Types

Fixed low and high alarm peak levels, high alarm activation will latch and isolate the connected gas valve.

Peak Alarms

Methane/Natural Gas (CH4) & Propane (C3H8)
• 5% low alarm
• 10% high alarm

Carbon Monoxide (CO)
• 20PPM Low Alarm
• 30PPM High Alarm

Carbon Dioxide (CO2)
• 2800PPM Low Alarm
• 5000PPM High Alarm

Carbon Dioxide (CO2) – High Mode Selectable by Sensor
• 5000PPM Low Alarm
• 10000PPM High Alarm

Oxygen (O2) Depletion
• 19.5% Pre Alarm
• 18% Full Alarm

Warranty

Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of our products.
This applies to the main panel; gas detectors carry a two-year warranty.

Where we commission an installed system the warranty is extended from five to ten years. At the time of commissioning, photos and gas pressure readings are recorded along with other relevant details of the installation. A 24-hour helpline number and the serial number is attached with the panel and all details are then entered on to the Medem database.

Service

The panel and sensors must be re-commissioned and tested every 12 months as a minimum but with consideration of every 6 months dependant on gas type and environment.