SEC-K (NP)

The SEC-K is a ventilation interlock system for commercial kitchens with multiple in-built features which can be used where and when required to help sites meet BS 6173/2009 & IGEM UP19.

The recently updated V4 system can monitor for carbon monoxide (CO) and carbon dioxide (CO2) out of hours so even when the panel is switched off an alarm can be raised, or ventilation switched on. This provides additional safety monitoring particularly if solid fuel appliances are installed within the kitchen.

Demand-controlled ventilation fail-safe gas valve and relay checking are just some of the new developments making Medem systems continue to be the most reliable, safest and flexible available today.


If you require further information about this product please call us on 0161 233 0600 or email at enquiries@medem.co.uk and we’ll be more than happy to help.

Description

> Ventilation Interlock <
> Carbon Dioxide Level Monitoring <
> Carbon Monoxide Gas Detection <
> Demand Controlled Ventilation <
> Dual BMS selectable relays <
> Fire Test Isolation Control Built-in <
> CO2 based ventilation activation <
> CO2 based ventilation control <
> Electrical Isolation <
> Engineer Functions <
> Fan interlocking <

Out of hours CO and CO2 monitoring, fail-safe gas valve and relay checking are just some of the new developments making Medem systems continue to be the most reliable, safest and flexible available today.

 


Product and Installation Guides
⤓ SEC-K (NP) | Product and Installation Guide



Related Standards
 > BS6173
 > UP19

 


All our products come with a 5-year warranty
Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of its products.
This applies to the main panels and sender units, gas detectors carry a 2-year warranty.

Why not let us install your system and receive a 10-year Warranty?
Where we’ve commissioned an installed system, the warranty is extended from five to ten years. At the time of commissioning, photos and gas pressure readings are recorded along with other relevant details of the installation. A 24-hour helpline number and the serial number is attached with the panel and all details are then entered on to the Medem database.

 

Additional information

Product Dimensions

212mm x 183mm x 97mm

Gas Detection

The panel can monitor up to 6 detectors directly and up to 16 when installed with an AD-PP power pack. The current range is:
Methane/Natural Gas (CH4), Propane (C3H8), Carbon Monoxide (CO) Carbon Dioxide (CO2) and Oxygen (O2) Depletion

Alarm Types

Fixed low and high alarm peak levels, high alarm activation will latch and isolate the connected gas valve.

Peak Alarms

Methane/Natural Gas (CH4) & Propane (C3H8)
• 5% low alarm
• 10% high alarm

Carbon Monoxide (CO)
• 20PPM Low Alarm
• 30PPM High Alarm

Carbon Dioxide (CO2) – Selectable
• 1500PPM
• 2200PPM
• 2800PPM
• 4000PPM
• 5000PPM

Oxygen (O2) Depletion
• 19.5% Pre Alarm
• 18% Full Alarm

Warranty

Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of our products.

This applies to the main panel; gas detectors carry a two-year warranty.

Where we commission an installed system the warranty is extended from five to ten years. At the time of commissioning, photos and gas pressure readings are recorded along with other relevant details of the installation. A 24-hour helpline number and the serial number is attached with the panel and all details are then entered on to the Medem database.

Service

The panel and sensors must be re-commissioned and tested every 12 months as a minimum but with consideration of every 6 months dependant on gas type and environment.

Medem offers cost-effective yearly service plan options which include detector exchange to assist in service budgeting.