SACO2

LEGACY PRODUCT ONLY

This system has now been superseded by the SEC-B.

Gas detection and pressure proving system.

CO2 Detection designed for schools and colleges.

CO2 is now considered a primary indicator of air quality, with the latest legislation setting maximum limits for levels within education facilities.

With the SACO2 carbon dioxide levels can be continually monitored in rooms such as teaching areas or offices. The panel and sensors have been developed to enable compliance with these latest standards.

These include the Department of Education building bulletin 101 (BB101), the supporting document to the building regulations part F. The BB101 states that the maximum level of carbon dioxide in the air within a classroom should be no more than 1,500 parts per million (PPM).

The SACO2 can be installed and used as a standalone unit with one or two carbon dioxide sensors model AD-MED-CO2 fitted. As a standalone system, the panel will indicate a pre-alarm at 900ppm by means of a visual indication on the panel fascia. The panel will indicate full alarm at 1,500ppm, again with visual indication on the panel. A sounder is fitted within the panel and is factory preset to silent but can be activated by means of jumper plug adjustment where an audible indication is required. The system will drop out of the alarm condition as the carbon dioxide level.

The SACO2 also has two NO/NC contacts which change state at the pre-alarm and full-alarm levels, these can be used for controlling any mechanical ventilation in the room.


If you require further information about this product please call us on 0161 233 0600 or email at enquiries@medem.co.uk and we’ll be more than happy to help.

 

Category:

Description

This product is no longer available. If you need assistance with an already installed unit, please get in touch and we’ll help.

 


All our products come with a 5-year warranty
Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of its products.
This applies to the main panels and sender units, gas detectors carry a 2-year warranty.

Why not let us install your system and receive a 10-year Warranty?
Where we’ve commissioned an installed system, the warranty is extended from five to ten years. At the time of commissioning, photos and gas pressure readings are recorded along with other relevant details of the installation. A 24-hour helpline number and the serial number is attached with the panel and all details are then entered on to the Medem database.